- Monitoring of BNS range magnetic safety sensors
- 2 safety contacts, STOP 0
- 4 Signalling outputs
Ordering data
Note (Delivery capacity) | Phased-out product |
Product type description | AES 3075 24 VDC |
Article number (order number) | 101138576 |
EAN (European Article Number) | 4030661281360 |
eCl@ss number, Version 9.0 | 27-37-18-19 |
eCl@ss number, Version 11.0 | 27-37-18-19 |
ETIM number, version 6.0 | EC001449 |
Approval - Standards
Certificates | BG cULus EAC |
General data
Standards | IEC/EN 60204-1 IEC 60947-5-3 BG-GS-ET-14 BG-GS-ET-20 EN ISO 13849-1 |
Enclosure material | Glass-fibre, reinforced thermoplastic |
Gross weight | 379 g |
General data - Features
Stop-Category | 0 |
Wire breakage detection | Yes |
Short-circuit recognition | Yes |
Start input | Yes |
Feedback circuit | Yes |
Automatic reset function | Yes |
Integral System Diagnostics, status | Yes |
Number of LEDs | 1 |
Number of openers | 4 |
Number of shutters | 4 |
Number of undelayed semi-conductor outputs with signaling function | 4 |
Number of safety contacts | 2 |
Number of signalling outputs | 4 |
Safety appraisal
Standards | EN ISO 13849-1 IEC 61508 |
Safety appraisal - Relay outputs
Performance Level, up to | d |
Control category to EN13849 | 3 |
PFH-value | 1.00 x 10⁻⁷ /h |
Notice | for max. 50,000 switching cycles/year and max. 80% contact load |
Safety Integrity Level (SIL), suitable for applications in | 2 |
Mission time | 20 Year(s) |
Mechanical data
Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data - Connection technique
Terminal Connector | Screw connection |
Cable section, maximum | 4 mm² |
Note (Cable section) | All indications about the cable section are including the conductor ferrules. |
Tightening torque of Clips | 0.4 Nm |
Mechanical data - Dimensions
Width | 75 mm |
Height | 100 mm |
Depth | 110 mm |
Ambient conditions
Degree of protection of the enclosure | IP40 |
Degree of protection of the mounting space | IP54 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature, minimum | +0 °C |
Ambient temperature, maximum | +55 °C |
Storage and transport temperature, minimum | -25 °C |
Storage and transport temperature, maximum | +70 °C |
Resistance to vibrations to EN 60068-2-6 | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
Ambient conditions - Insulation value
Rated impulse withstand voltage Uimp | 0.5 kV |
Overvoltage category | III |
Degree of pollution to IEC/EN 60664-1 | 2 |
Electrical data
Frequency range | 50 Hz 60 Hz |
Thermal test current | 4 A |
Rated operating voltage | 24 VAC -15% / +10% 24 VDC -10%/+20%, residual ripple max. 10% |
Rated AC voltage for controls, 50 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 50 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls, 60 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 60 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls at DC minimum | 20.4 VDC |
Rated control voltage at DC, maximum | 28.8 VDC |
Electrical power consumption | 8 W |
Contact resistance, maximum | 0.1 Ω |
Note (Contact resistance) | in new state |
Drop-out delay in case of power failure, typically | 80 ms |
Drop-out delay in case of emergency, typically | 20 ms |
Pull-in delay at automatic start, maximum, typically | 100 ms |
Pull-in delay at RESET, typically | 20 ms |
Electrical data - Safe relay outputs
Voltage, Utilisation category AC15 | 230 VAC |
Current, Utilisation category AC-15 | 6 A |
Voltage, Utilisation category DC13 | 24 VDC |
Current, Utilisation category DC13 | 6 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 8 A |
Electrical data - Digital inputs
Input signal, HIGH Signal 1 | 10 … 30 VDC |
Input signal, LOW Signal 0 | 0 … 2 VDC |
Conduction resistance, maximum | 40 Ω |
Electrical data - Digital Output
Voltage, Utilisation category DC12 | 24 VDC |
Current, Utilisation category DC12 | 0.1 A |
Electrical data - Relay outputs (auxiliary contacts)
Switching capacity, maximum | 24 VDC |
Switching capacity, maximum | 2 A |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating | EMC-Directive |
Integral system diagnosis (ISD)
Note (ISD -Faults) | The following faults are registered by the safety monitoring modules and indicated by ISD. |
Faults | Failure of door contacts to open or close Cross-wire or short-circuit monitoring of the switch connections Interruption of the switch connections Fault on the input circuits or the relay control circuits of the safety monitoring module |
Other data
Note (applications) | Safety sensor Guard system |
Notes
Note (General) | Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Circuit example
Note (Wiring diagram) | The wiring diagram is shown with guard doors closed and in de-energised condition. The ISD tables (Intergral System Diagnostics) for analysis of the fault indications and their causes are shown in the appendix. Start push button: A start push button (NO) can optionally be connected into the feedback circuit. With the guard door closed, the enabling paths are then not closed until the start push button has been operated. The feedback circuit monitors the position of the positive-guided NC contacts of the contactors K3 and K4. To secure 4 guard doors up to PL d and Category 3 Monitoring 4 guard door(s), each with a magnetic safety sensor of the BNS range The NC contacts of the external contactors must be wired in series to X1 (+) and X2. If less than 4 switches are connected, the unused terminals S21/S22 must be bridged before a NC contact is connected. This applies to the position of the jumpers in the safety-monitoring module with NC/NO configuration. The switch (H6) connected to terminals X3 and X4 switches the enabling outputs Y14 and Y24 on and off with the guard door closed. If no switch is connected, a jumper connection must be mounted between the terminals X3 and X4. |