- Actuator monitored
- Solenoid interlock
- Integrated AS-Interface
- Thermoplastic enclosure
- 90 mm x 84 mm x 30 mm
- Double-insulated
- High holding force
Ordering data
Product type description | AZM 170 B ST-AS P |
Article number (order number) | 101210928 |
EAN (European Article Number) | 4030661390420 |
eCl@ss number, Version 9.0 | 27-27-26-03 |
eCl@ss number, Version 11.0 | 27-27-26-03 |
Approval - Standards
Certificates | TÜV cULus ASi-SaW EAC |
General data
Standards | IEC 61508 EN 60947-5-1 EN 62026-2 EN ISO 13849-1 |
Active principle | electromechanical |
Enclosure material | Plastic, glass-fibre reinforced thermoplastic, self-extinguishing |
Gross weight | 300 g |
Reaction time, maximum | 100 ms |
General data - Features
Power to unlock | Yes |
Actuator monitored | Yes |
Integral System Diagnostics, status | Yes |
Number of actuating directions | 2 |
Safety appraisal
Standards | IEC 61508 | |
Performance level, up to | c | |
Control category to EN13849 | 1 | |
PFH-value | 1.16 x 10⁻⁶ /h | |
Note (PFH-value) | up to max. 100,000 switching cycles/year | |
| 1 | |
Mission Time | 20 Year(s) |
Safety appraisal - Fault exclusion
Please note: | Einsetzbar wenn ein Fehlerausschluss für eine gefahrbringende Beschädigung der 1-kanaligen Mechanik zulässig ist und ein ausreichender Manipulationsschutz gewährleistet ist. |
Performance Level, up to | d |
Control category to EN13849 | 3 |
PFH-value | 1.01 x 10⁻⁷ /h |
Note (PFH-value) | up to max. 100,000 switching cycles/year |
Safety Integrity Level (SIL), suitable for applications in | 2 |
Mission time | 20 Year(s) |
Mechanical data
Mechanical life, minimum | 1,000,000 Operations |
Clamping force | 1,000 N |
Latching force | 5 N |
Actuating speed, maximum | 2 m/s |
Mechanical data - Connection technique
Terminal Connector | Connector plug M12, 4-pole, (A-coding) |
Mechanical data - Dimensions
Width of sensor | 90 mm |
Height of sensor | 75.5 mm |
Ambient conditions
Degree of protection | IP67 to EN 60529 |
Ambient temperature, minimum | -25 °C |
Ambient temperature, maximum | +55 °C |
Storage and transport temperature, minimum | -25 °C |
Storage and transport temperature, maximum | +85 °C |
Relative humidity, minimum | 30 % |
Relative humidity, maximum | 95 % |
Note (Relative humidity) | non-condensing non-icing |
Protection rating | II |
Ambient conditions - Insulation value
Rated insulation voltage Ui | 32 VDC |
Rated impulse withstand voltage Uimp | 0.8 kV |
Overvoltage category | III |
Degree of pollution to VDE 0100 | 3 |
Electrical data - AS Interface
AS-i Operating voltage, minimum | 26.5 VDC |
AS-i Operating voltage AS-i maximum | 31.6 VDC |
Note (AS-i Operating voltage) | Protection against polarity reversal |
AS-i Current consumption, maximum | 100 mA |
Electrical data - AS-Interface specification
AS-i Specification | Safety-Slave |
AS-i Version | V 2.1 |
AS-i Profile | S-7.B.F.E |
AS-i, IO-Code | 0x7 |
AS-i, ID-Code | 0xB |
AS-i, ID-Code1 | 0xF |
AS-i, ID-Code2 | 0xE |
AS-i Input, Channel 1 | Data bits DI 0 / DI 1 = dynamic code transmission |
AS-i Input, Channel 2 | Data bits DI 2 / DI 3 = dynamic code transmission |
AS-i Outputs, DO 0 | Solenoid control |
AS-i Outputs, DO 1 | No Function |
AS-i Outputs, DO 2 | No Function |
AS-i Outputs, DO 3 | No Function |
AS-i Parameter bits, P0 | Safety guard and actuator detected |
AS-i Parameter bits, P1 | Solenoid interlock locked |
AS-i Parameter bits, P2 | No function |
AS-i Parameter bits, P3 | No function |
Note (AS-i Parameter bits) | Set the parameter outputs to '1111' (0xF) FID: periphery error |
AS-i Input module address | 0 |
Note (AS-i Input module address) | Preset to address 0, can be changed through AS-interface bus master or hand-held programming device |
Electrical data - Auxiliary voltage
Rated operating voltage | 24 VDC -15% / +10% (stabilised PELV) |
Operating current | 500 mA |
Status indication
Note (LED switching conditions display) | (1) LED green: Supply voltage (2) red LED: Communication error / Slave address = 0 (3) LED yellow : Enabling status |
Pin assignment
PIN 1 | AS-i + |
PIN 2 | Aux - (P) |
PIN 3 | AS-Interface - |
PIN 4 | Aux + (P) |
Scope of delivery
Included in delivery | Actuators must be ordered separately. |
Notes
Note (General) | Interlocks with the power to lock principle may only be used in special cases after a thorough evaluation of the accident risk, since the guarding device can immediately be opened on failure of the electrical power supply or when the main switch is opened. |