  • Suitable for the signal processing of outputs with contact sensors
  • Suitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains
  • Suitable for the signal processing of outputs with contact sensors
  • 3 safety contacts, STOP 0
  • 1 Signalling output

Ordering data

Product type description

SRB301ST-24V-(V.3)

Article number (order number)

103002205

EAN (European Article Number)

4030661562186

eCl@ss number, Version 9.0

27-37-18-19

eCl@ss number, Version 11.0

27-37-18-19

ETIM number, version 6.0

EC001449

Available until

31.12.2022

Approval - Standards

Certificates

TÜV

cULus

CCC

EAC

TILVA

General data

Standards

IEC 61508

IEC/EN 60204-1

EN 60947-5-1

EN 81-20/-50

EN ISO 13849-1

Climatic stress

EN 60068-2-78

Enclosure material

Glass-fibre reinforced thermoplastic, ventilated

Material of the contacts, electrical

AgSn0. self-cleaning, positive drive

Gross weight

250 g

General data - Features

Stop-Category

0

Electronic Fuse

Yes

Wire breakage detection

Yes

Short-circuit recognition

Yes

Removable Terminals

Yes

Start input

Yes

Feedback circuit

Yes

Automatic reset function

Yes

Reset edge detection

Yes

Earth connection detection

Yes

Integral System Diagnostics, status

Yes

Number of auxiliary contacts

1

Number of LEDs

5

Number of openers

2

Number of safety contacts

3

Safety appraisal

Standards

EN ISO 13849-1

EN 62061

IEC 61508

Safety appraisal - Relay outputs

Performance level, stop 0, up to

e

Category, Stop 0

4

Diagnostic Coverage (DC) Level, Stop 0

≥ 99 %

PFH-Value Stop 0

2.00 x 10⁻⁸ /h

Safety Integrity Level (SIL), Stop 0, suitable for applications in

3

Mission time

20 Year(s)

Common Cause Failure (CCF), minimum

65

Mechanical data

Mechanical life, minimum

10,000,000 Operations

Mounting

Snaps onto standard DIN rail to EN 60715

Mechanical data - Connection technique

Terminal Connector

Screw connection, plug-in

rigid or flexible

Terminal designations

IEC/EN 60947-1

Cable section, minimum

0.25 mm²

Cable section, maximum

2.5 mm²

Tightening torque of Clips

0.6 Nm

Mechanical data - Dimensions

Width

22.5 mm

Height

120 mm

Depth

121 mm

Ambient conditions

Degree of protection of the enclosure

IP40

Degree of protection of the mounting space

IP54

Degree of protection of clips or terminals

IP20

Ambient temperature, minimum

-25 °C

Ambient temperature, maximum

+60 °C

Storage and transport temperature, minimum

-40 °C

Storage and transport temperature, maximum

+85 °C

Resistance to vibrations to EN 60068-2-6

10 ... 55 Hz, Amplitude 0.35 mm

Restistance to shock

30 g / 11 ms

Ambient conditions - Insulation value

Rated impulse withstand voltage Uimp

4 kV

Overvoltage category

III

Degree of pollution to IEC/EN 60664-1

2

Electrical data

Frequency range

50 Hz

60 Hz

Rated operating voltage

24 VAC -15% / +10%

24 VDC -15%/+20%, residual ripple max. 10%

Rated AC voltage for controls, 50 Hz, minimum

20.4 VAC

Rated control voltage at AC 50 Hz, maximum

26.4 VAC

Rated AC voltage for controls, 60 Hz, minimum

20.4 VAC

Rated control voltage at AC 60 Hz, maximum

26.4 VAC

Rated AC voltage for controls at DC minimum

20.4 VDC

Rated control voltage at DC, maximum

28.8 VDC

Electrical power consumption

2 W

Electrical power consumption

4.9 VA

Contact resistance, maximum

0.1 Ω

Note (Contact resistance)

in new state

Drop-out delay in case of power failure, typically

80 ms

Drop-out delay in case of emergency, typically

20 ms

Pull-in delay at automatic start, maximum, typically

100 ms

Pull-in delay at RESET, typically

20 ms

Electrical data - Safe relay outputs

Voltage, Utilisation category AC15

230 VAC

Current, Utilisation category AC-15

6 A

Voltage, Utilisation category DC13

24 VDC

Current, Utilisation category DC13

6 A

Switching capacity, minimum

10 VDC

Switching capacity, minimum

10 mA

Switching capacity, maximum

250 VAC

Switching capacity, maximum

8 A

Electrical data - Digital inputs

Conduction resistance, maximum

40 Ω

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum

24 VDC

Switching capacity, maximum

2 A

Electrical data - Electromagnetic compatibility (EMC)

EMC rating

EMC-Directive

Status indication

Note (LED switching conditions display)

QS: cross-wire short detection status (LED on when cross-wire short detection active).

Indicated operating states

Position relay K2

Position relay K1

Internal operating voltage Ui

Other data

Note (applications)

Safety sensor

Guard system

Emergency-Stop button

Pull-wire emergency stop switches

Safety light barriers

Notes

Note (General)

Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.

Circuit example

Note (Wiring diagram)

The wiring diagram is shown with guard doors closed and in de-energised condition.

Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2).

Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts.

The control recognises cross-short, cable break and earth leakages in the monitoring circuit.

Switch setting: The cross-wire short detection function (factory default) is programmed by means of the switch located underneath the front cover of the module: Pposition nQS (top): no cross-wire short protection, suitable for 1-channel applications and applications with outputs with potential in the control circuits. Position QS (bottom): cross-wire short protection, suitable for 2-channel applications without outputs with potential in the control circuits.

For 1-channel control, connect NC contact to S11/S12 and bridge S12/S22 (QS-switch = nQS)

Connect potential p-type outputs of safety light grids/curtains to S12/S22. The devices must have the same reference potential. QS-switch = nQS

Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals S12/X3. If the feedback circuit is not required, establish a bridge.

F1 = Hybrid fuse

Наш менеджер свяжется с вами в ближайшее время