- 3 cable entries M 16 x 1.5
- Ex-Zone 22
- Thermoplastic enclosure
- Universal coding
- 52 mm x 90 mm x 30 mm
- High level of contact reliability with low voltages and currents
- Slotted holes for adjustment, circular holes for location
- Double-insulated
- For intrinsically safe current circuits (Ex i) to Ex-Zone 0 and 20
Ordering data
Product type description | EX-AZ 16-12ZVRK-3D |
Article number (order number) | 101185377 |
EAN (European Article Number) | 4030661324883 |
eCl@ss number, Version 9.0 | 27-27-06-02 |
eCl@ss number, Version 11.0 | 27-27-06-02 |
ETIM number, version 6.0 | EC001829 |
ETIM number, version 7.0 | EC001829 |
Explosion protection
Explosion protection: regulations | EN 60079-0 |
Explosion protection zones | 22 |
Explosion protection category | 3D |
Explosion protection designation | D II 3D Ex tc IIIC T90°C Dc X |
Manufacturer declaration | ATEX Zone 22 |
General data
Coding level according to ISO 14119 | Low |
Enclosure material | Plastic, glass-fibre reinforced thermoplastic, self-extinguishing |
Material of the contacts, electrical | Silver |
Gross weight | 145 g |
General data - Features
higher Latching force | Yes |
Number of auxiliary contacts | 1 |
Number of safety contacts | 2 |
Safety appraisal
Standards | EN ISO 13849-1 |
Mission Time | 20 Year(s) |
Safety appraisal - Safety outputs
B10d Normally-closed contact (NC) | 2,000,000 Operations |
B10d Normally open contact (NO) | 1,000,000 Operations |
Note (B10d Normally open contact (NO)) | at 10% Ie and ohmic load |
Mechanical data
Mechanical life, minimum | 1,000,000 Operations |
Latching force | 30 N |
positive break travel | 8 mm |
Positive break force, minimum | 10 N |
Actuating speed, maximum | 1 m/s |
Mechanical data - Connection technique
Terminal Connector | Screw connection |
Cable cross-section of the cable glands, minimum | 6 mm |
Cable cross-section of the cable glands, maximum | 12 mm |
Cable section, minimum | 0.75 mm² |
Cable section, maximum | 2.5 mm² |
Note (Cable section) | All indications about the cable section are including the conductor ferrules. |
Mechanical data - Dimensions
Length of sensor | 30 mm |
Width of sensor | 52 mm |
Height of sensor | 90 mm |
Ambient conditions
Degree of protection | IP67 to EN 60529 |
Ambient temperature, minimum | -20 °C |
Ambient temperature, maximum | +70 °C |
Ambient conditions - Insulation value
Rated insulation voltage Ui | 500 V |
Rated impulse withstand voltage Uimp | 6 kV |
Electrical data
Thermal test current | 2.5 A |
Utilisation category AC-15 | 230 VAC |
Utilisation category AC-15 | 2.5 A |
Utilisation category DC-13 | 24 VDC |
Utilisation category DC-13 | 2.5 A |
Switching element | NO contact, NC contact |
Switching principle | Creep circuit element |
Scope of delivery
Included in delivery | Actuators must be ordered separately. Slot sealing plugs Including Ex-certified screwed cable gland and screw plug |
Notes
Note (General) | Individual coding available on request |