Бренды по алфавиту:
А Б В Г Д Е Ё Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Ъ Ы Ь Э Ю Я
Работаем с юридическими лицами, бюджетными организациями, ИП
По вопросам приобретения товара пишите на zakaz@lanfor.ru
Оплата по безналичному расчету согласно выставленному счету
Самовывоз - бесплатно, от 300руб. до пункта выдачи в Вашем городе, доставка от 500руб. "до двери"
  • Metal enclosure
  • two-side operation / wire up to 2 x 50 m long
  • Robust design
  • Low actuating force
  • Ex certified
  • Pull-ring reset
  • wire pull and breakage detection
  • Ex-Zone 21 and 22

Ordering data

Product type description

EX-T3Z 068-33YR-1637

Article number (order number)

101218074

EAN (European Article Number)

4030661415215

eCl@ss number, Version 9.0

27-37-12-01

eCl@ss number, Version 11.0

27-37-12-01

ETIM number, version 6.0

EC002026

Approval - Standards

Certificates

TÜV

INMETRO

CCC

CCC EX

Explosion protection

Explosion protection: regulations

EN 60079-31

IEC 60079-0

ABNT NBR IEC 60079-0

ABNT NBR IEC 60079-31

Explosion protection zones

21

Explosion protection category

2D

Explosion protection designation

D II 2D Ex tb IIIC T90°C Db

General data

Standards

EN 60947-5-1

EN ISO 13850

EN 60947-5-5

ABNT NBR IEC 60947-5-1

ABNT NBR IEC 60947-5-5

Enclosure material

Grey cast iron, painted

Material of the contacts, electrical

Silver

Material of the cover

Grey cast iron, painted

Length of the wire, maximum

50 m

Gross weight

4,500 g

General data - Features

Reset by pull ring

Yes

Number of auxiliary contacts

3

Number of safety contacts

3

Safety appraisal

Standards

EN ISO 13849-1

Mission Time

20 Year(s)

Safety appraisal - Safety outputs

B10d Normally-closed contact (NC)

100,000 Operations

Mechanical data

Actuating element

Roller lever N300

Mechanical life, minimum

50,000 Operations

Positive break angle

32 °

Actuating force, maximum

50 N

Note (Actuating force)

30 N in wire direction

Actuation direction

Each time 75° right-hand side and left-hand side rotation

Positive break force, minimum

50 N

Positive break torque

0.2 Nm

Mechanical data - Connection technique

Terminal Connector

Screw connection

Cable section, minimum

0.75 mm²

Cable section, maximum

1.5 mm²

Ambient conditions

Degree of protection

ABNT NBR IEC 60529

IP65 to EN 60529

IP66 to EN 60529

Ambient temperature, minimum

-20 °C

Ambient temperature, maximum

+60 °C

Ambient conditions - Insulation value

Rated insulation voltage Ui

250 V

Rated impulse withstand voltage Uimp

4 kV

Electrical data

Thermal test current

10 A

Utilisation category AC-15

230 VAC

Utilisation category AC-15

2.5 A

Utilisation category DC-13

24 VDC

Utilisation category DC-13

6 A

Switching element

NO contact, NC contact

Switching principle

Snap switch element

Notes

Note (General)

At 3 m distance intermediate wire supports are required, see accessories