  • Thermoplastic enclosure
  • AC 2-wire
  • Wiring compartment can be turned 180°
  • Design M30
  • Wiring compartment

Ordering data

Product type description

IFOD 8-300-10/01

Article number (order number)

103038715

EAN (European Article Number)

4030661545967

eCl@ss number, Version 9.0

27-27-08-01

eCl@ss number, Version 11.0

27-27-08-01

ETIM number, version 6.0

EC001825

ETIM number, version 7.0

EC001825

General data

Standards

IEC/EN 60947-5-2

DIN VDE 0660-208

Housing construction form

Cylinder, thread

Enclosure material

Plastic

Active area

Plastic

Material of the nuts

Plastic

Material of the washer

Perbunan®

Detection range, maximum Sd

800 mm

Gross weight

72.2 g

General data - Features

Integral System Diagnostics, status

Yes

Number of cable wires

2

Mechanical data

Tightening torque of nuts, maximum

4 Nm

Mechanical data - Connection technique

Terminal Connector

Screw connection

Cable section, maximum

2 x 1.5 mm²

Wire cross-section

15 AWG

Mechanical data - Dimensions

ISO thread of the sensor

M30

width across flats

36 BK

Length of sensor

118 mm

Width of sensor

46 mm

Height of sensor

46 mm

Ambient conditions

Degree of protection

IP65 to EN 60529

Ambient temperature, minimum

-5 °C

Ambient temperature, maximum

+70 °C

Protection rating

II

Ambient conditions - Insulation value

Rated impulse withstand voltage Uimp

10 kV

Electrical data

Voltage type

AC (alternating current)

Rated supply frequency, minimum

45 Hz

Rated supply frequency, maximum

65 Hz

Operating voltage, minimum

15 V

Operating voltage, maximum

250 V

Operating current, minimum

10 mA

Operating current

500 mA

Switching element

NO contact or NC contact

Protection circuit integrated

inductive interference protection

Switching frequency, approx.

10 Hz

Electrical data - Digital Output

Voltage drop Ud, maximum

7 V

Current at Voltage drop Ud

0.5 A

Versions

Two-wire

Current leakage Ir

3 mA

Status indication

Note (Integral System Diagnostics, status )

yellow LED