- PROFIBUS Gateway SD-I-DP-V0-2 to convert serial diagnostic signals to the PROFIBUS DP protocol
- The PROFIBUS Gateway SD-I-DP-V0-2 is a PROFIBUS slave
- Protection class IP 10 device for control cabinet mounting, for standard DIN rails
Ordering data
| Product type description | SD-I-DP-V0-2 PROFIBUS-GATEWAY |
| Article number (order number) | 101192805 |
| EAN (European Article Number) | 4030661353951 |
| eCl@ss number, Version 9.0 | 27-23-02-08 |
General data
| Gross weight | 120 g |
General data - Features
| Integral System Diagnostics, status | Yes |
| Number of LEDs | 4 |
Mechanical data
| Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data - Connection technique
| Terminal Connector | Cage clamps |
Mechanical data - Dimensions
| Width | 50 mm |
| Height | 72 mm |
| Depth | 97 mm |
Ambient conditions
| Degree of protection of the enclosure | IP10 |
| Ambient temperature, minimum | -5 °C |
| Ambient temperature, maximum | +55 °C |
| Storage and transport temperature, minimum | -25 °C |
| Storage and transport temperature, maximum | +85 °C |
| Resistance to vibrations to EN 60068-2-6 | 5 ... 9 Hz, Amplitude 3.5 mm 9 ... 150 Hz, with 1 g |
| Restistance to shock | 15 g / 11 ms |
Ambient conditions - Insulation value
| Rated insulation voltage Ui | 32 V |
| Rated impulse withstand voltage Uimp | 0.5 kV |
| Overvoltage category | II |
| Degree of pollution to VDE 0110 | 2 |
Electrical data
| Rated operating voltage | 24 VDC, - 15 % / + 20 % (stabilised PELV) |
| Operating current | 250 mA |
Status indication
| Note (LED switching conditions display) | ON permanent light green: supply voltage present PB Flashing signal: PROFIBUS initialisation PB Permanent light red: PROFIBUS error SD Flashing signal: = SD gateway initialisation SD Permanent light Red: = SD Gateway fault |
Other data
| Note (applications) | Safety sensor Guard system |
Notes
| Note (General) | Detailed functions, see programming and configuration manual of the SD Gateway |
Circuit example
| Note (Wiring diagram) | Serial diagnostics of series-wired safety sensors/solenoid interlocks Devices with serial diagnostic option: AZ 200, AZM 200, CSS 30S, CSS 34, MZM 100 |