        - Thermoplastic enclosure
- AC 2-wire
- Wiring compartment can be turned 180°
- Design M30
- Wiring compartment
Ordering data
| Product type description | IFOD 8-300-10/01 | 
| Article number (order number) | 103038715 | 
| EAN (European Article Number) | 4030661545967 | 
| eCl@ss number, Version 9.0 | 27-27-08-01 | 
| eCl@ss number, Version 11.0 | 27-27-08-01 | 
| ETIM number, version 6.0 | EC001825 | 
| ETIM number, version 7.0 | EC001825 | 
General data
| Standards | IEC/EN 60947-5-2 DIN VDE 0660-208 | 
| Housing construction form | Cylinder, thread | 
| Enclosure material | Plastic | 
| Active area | Plastic | 
| Material of the nuts | Plastic | 
| Material of the washer | Perbunan® | 
| Detection range, maximum Sd | 800 mm | 
| Gross weight | 72.2 g | 
General data - Features
| Integral System Diagnostics, status | Yes | 
| Number of cable wires | 2 | 
Mechanical data
| Tightening torque of nuts, maximum | 4 Nm | 
Mechanical data - Connection technique
| Terminal Connector | Screw connection | 
| Cable section, maximum | 2 x 1.5 mm² | 
| Wire cross-section | 15 AWG | 
Mechanical data - Dimensions
| ISO thread of the sensor | M30 | 
| width across flats | 36 BK | 
| Length of sensor | 118 mm | 
| Width of sensor | 46 mm | 
| Height of sensor | 46 mm | 
Ambient conditions
| Degree of protection | IP65 to EN 60529 | 
| Ambient temperature, minimum | -5 °C | 
| Ambient temperature, maximum | +70 °C | 
| Protection rating | II | 
Ambient conditions - Insulation value
| Rated impulse withstand voltage Uimp | 10 kV | 
Electrical data
| Voltage type | AC (alternating current) | 
| Rated supply frequency, minimum | 45 Hz | 
| Rated supply frequency, maximum | 65 Hz | 
| Operating voltage, minimum | 15 V | 
| Operating voltage, maximum | 250 V | 
| Operating current, minimum | 10 mA | 
| Operating current | 500 mA | 
| Switching element | NO contact or NC contact | 
| Protection circuit integrated | inductive interference protection | 
| Switching frequency, approx. | 10 Hz | 
Electrical data - Digital Output
| Voltage drop Ud, maximum | 7 V | 
| Current at Voltage drop Ud | 0.5 A | 
| Versions | Two-wire | 
| Current leakage Ir | 3 mA | 
Status indication
| Note (Integral System Diagnostics, status ) | yellow LED | 