        - Memory card
 - conversion of the field bus protocols by software
 - integrated SD-Bus-Gateway
 - Modular expansion with up to 64 inputs / outputs
 - 4 safe 2 A pp-switching semiconductor outputs, switchable to 2 safe p- / n-switching semiconductor outputs
 - 14 safe inputs on the base module
 - 2 Signalling outputs
 - 2 safety relay contacts
 
Ordering data
| Product type description |   PSC1-C-10-FB2  |  
| Article number (order number) |   103008442  |  
| EAN (European Article Number) |   4030661458373  |  
| eCl@ss number, Version 9.0 |   27-24-22-07  |  
| eCl@ss number, Version 11.0 |   27-24-22-07  |  
| ETIM number, version 6.0 |   EC000236  |  
Approval - Standards
| Certificates |   TÜV cULus EAC  |  
General data
| Terminal (mechanical) |   Removable screw terminals  |  
| Gross weight |   582.1 g  |  
General data - Features
| SD Card Slot |   Yes  |  
| Master-Slave-Kommunikation |   Yes  |  
| Master-Master-Kommunikation |   Yes  |  
| Integrated SD gateway |   Yes  |  
| Number of pulse outputs (test pulse output) |   2  |  
| Number of relay outputs (1-channel) |   2  |  
| Number of digital fail-safe inputs |   14  |  
| Number of fail-safe digital outputs |   4  |  
| Number of signalling outputs |   2  |  
| Anzahl der Erweiterungsbaugruppen, maximal |   2  |  
Safety appraisal
| Performance level, up to |   e  |  |
| Control category to EN13849 |   4  |  |
| PFH-value |   1.26 x 10⁻⁸ /h  |  |
  |    3  |  |
| Mission Time |   20 Year(s)  |  
Mechanical data
| Mounting |   can be clipped into standard rail  |  
Mechanical data - Connection technique
| Cable section, minimum |   0.2 mm²  |  
| Cable section, maximum |   2.5 mm²  |  
| Wire cross-section, minimum |   24 AWG  |  
| Wire cross-section, maximum |   12 AWG  |  
Mechanical data - Dimensions
| Width |   67.5 mm  |  
| Height |   100 mm  |  
| Depth |   115 mm  |  
Ambient conditions
| Degree of protection |   IP20  |  
| Ambient temperature, minimum |   +0 °C  |  
| Ambient temperature, maximum |   +50 °C  |  
| Storage and transport temperature, minimum |   -25 °C  |  
| Storage and transport temperature, maximum |   +70 °C  |  
| Relative humidity, minimum |   5 %  |  
| Relative humidity, maximum |   85 %  |  
| Note (Relative humidity) |   non-condensing  |  
| Zulässige Aufstellhöhe über NN, maximum |   2,000 m  |  
Ambient conditions - Insulation value
| Overvoltage category |   III  |  
| Degree of pollution to IEC/EN 60664-1 |   2  |  
Electrical data
| Operating voltage, minimum |   20.4 VDC  |  
| Operating voltage, maximum |   28.8 VDC  |  
Electrical data - Universal communication interface
| Designation, Communication interface |   DSUB  |  
Electrical data - Communication protocols
| Field bus |   CANopen PROFIBUS  |  
Electrical data - Fail-safe digital outputs
| Rated operating current (safety outputs) |   2,000 mA  |  
| Versions |   short-circuit proof, p-type (Q2 und Q3)  |  
Electrical data - Safe relay outputs
| Voltage, Utilisation category AC15 |   230 VAC  |  
| Current, Utilisation category AC-15 |   2 A  |  
| Voltage, Utilisation category DC13 |   24 VDC  |  
| Current, Utilisation category DC13 |   2 A  |  
Electrical data - Electromagnetic compatibility (EMC)
| Electromagnetic compatibility |   DIN EN 62061 DIN EN 61800-3  |  
| Interfering radiation |   DIN EN 61000-6-4  |  
| EMC rating |   DIN EN 61000-6-7 DIN EN 61326-3 DIN EN 61000-6-2  |  
Scope of delivery
| Included in delivery |   Backplane bus connector Connector terminals  |  