- Possibility to connect up to 4 sensors with non-isolated signals, e.g. the CSS products from Schmersal as well as AOPD’s (only PROTECT-PE-02)
- Input for up to 4 sensors per interface e.g.: magnetic safety switches type BNS, emergency stop devices, interlocking devices and others
- Signalling output for each sensor (monitoring of both circuits of the sensors) and and all sensors (Y5, group signal)
- 2 safety contacts
Ordering data
| Product type description | PROTECT-PE-02 | 
| Article number (order number) | 101210948 | 
| EAN (European Article Number) | 4030661505862 | 
| eCl@ss number, Version 9.0 | 27-37-18-19 | 
| eCl@ss number, Version 11.0 | 27-37-18-19 | 
| ETIM number, version 6.0 | EC001449 | 
| Available until | 31.12.2022 | 
Approval - Standards
| Certificates | cULus EAC | 
General data
| Standards | IEC 61508 IEC/EN 60204-1 EN 60947-5-1 EN ISO 13849-1 | 
| Climatic stress | EN 60068-2-78 | 
| Enclosure material | Glass-fibre reinforced thermoplastic, ventilated | 
| Gross weight | 180 g | 
General data - Features
| Stop-Category | 0 | 
| Electronic Fuse | Yes | 
| Wire breakage detection | Yes | 
| Automatic reset function | Yes | 
| Earth connection detection | Yes | 
| Integral System Diagnostics, general | Yes | 
| Number of auxiliary contacts | 2 9 | 
| Number of LEDs | 6 | 
| Number of openers | 2 | 
| Number of signalling outputs | 7 | 
Safety appraisal
| Standards | EN 60947-5-1 IEC 61508 | 
Safety appraisal - Relay outputs
| Performance Level, up to | d | 
| Control category to EN13849 | 3 | 
| Diagnostic Coverage (DC) Level | 60 % | 
| PFH-value | 2.00 x 10⁻⁷ /h | 
| Safety Integrity Level (SIL), suitable for applications in | 2 | 
| Mission time | 20 Year(s) | 
| Common Cause Failure (CCF), minimum | 65 | 
Mechanical data
| Mechanical life, minimum | 10,000,000 Operations | 
| Mounting | Snaps onto standard DIN rail to EN 60715 | 
Mechanical data - Connection technique
| Terminal Connector | Cage clamps | 
| Terminal designations | IEC/EN 60947-1 | 
| Cable section, minimum | 0.2 mm² | 
| Cable section, maximum | 2.5 mm² | 
Mechanical data - Dimensions
| Width | 65.5 mm | 
| Height | 126 mm | 
| Depth | 61 mm | 
Ambient conditions
| Degree of protection of the enclosure | IP20 | 
| Degree of protection of the mounting space | IP20 | 
| Degree of protection of clips or terminals | IP20 | 
| Ambient temperature, minimum | -25 °C | 
| Ambient temperature, maximum | +55 °C | 
| Storage and transport temperature, minimum | -40 °C | 
| Storage and transport temperature, maximum | +85 °C | 
| Resistance to vibrations to EN 60068-2-6 | 10...55 Hz, Amplitude 0.35 mm, ± 15 % | 
| Restistance to shock | 30 g / 11 ms | 
Ambient conditions - Insulation value
| Rated impulse withstand voltage Uimp | 4 kV | 
| Overvoltage category | III | 
| Degree of pollution to VDE 0110 | 2 | 
Electrical data
| Rated operating voltage | 24 VDC -15% / +20%, residual ripple max. 10 % | 
| Rated AC voltage for controls, 50 Hz, minimum | 21.1 VAC | 
| Rated control voltage at AC 50 Hz, maximum | 26.4 VAC | 
| Rated AC voltage for controls, 60 Hz, minimum | 21.1 VAC | 
| Rated control voltage at AC 60 Hz, maximum | 26.4 VAC | 
| Rated AC voltage for controls at DC minimum | 21.1 VDC | 
| Rated control voltage at DC, maximum | 28.8 VDC | 
| Electrical power consumption | 1.7 W | 
| Input resistance at Ue | 2,900 Ω | 
| Contact resistance, maximum | 0.1 Ω | 
| Note (Contact resistance) | in new state | 
| Drop-out delay in case of power failure, maximum | 60 ms | 
| Drop-out delay in case of emergency stop, maximum | 10 ms | 
| Pull-in delay at automatic start, maximum, typically | 10 ms | 
Electrical data - Safe relay outputs
| Voltage, Utilisation category DC13 | 24 VDC | 
| Current, Utilisation category DC13 | 2 A | 
| Switching capacity, minimum | 10 VDC | 
| Switching capacity, minimum | 10 mA | 
| Switching capacity, maximum | 24 VAC | 
| Switching capacity, maximum | 2 A | 
Electrical data - Digital inputs
| Input signal, HIGH Signal 1 | 19 - 28,8 VDC | 
| Input signal, LOW Signal 0 | 0 - 1 VDC | 
| Conduction resistance, maximum | 40 Ω | 
Electrical data - Digital Output
| Voltage, Utilisation category DC12 | 24 VDC | 
| Current, Utilisation category DC12 | 0.1 A | 
Electrical data - Relay outputs (auxiliary contacts)
| Switching capacity, maximum | 24 VDC | 
| Switching capacity, maximum | 0.1 A | 
Electrical data - Electromagnetic compatibility (EMC)
| EMC rating | EMC-Directive | 
Status indication
| Indicated operating states | Position relay K2 Position relay K1 Internal operating voltage Ui Position relay K3 Position relay K3 | 
Other data
| Note (applications) | Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches Safety light curtain | 
 
                
 
                                         
                                         
                                         
                                         
                                         
                                         
                                 
                                 
                                 
                                 
                                 
                                
 
                   
                   
                  