- Input for up to 4 sensors per interface e.g.: magnetic safety switches type BNS, emergency stop devices, interlocking devices and others
- 2 safety contacts
Ordering data
| Product type description | PROTECT-IE-11-SK |
| Article number (order number) | 101189095 |
| EAN (European Article Number) | 4250116202232 |
| eCl@ss number, Version 9.0 | 27-37-18-19 |
| eCl@ss number, Version 11.0 | 27-37-18-19 |
| ETIM number, version 6.0 | EC001449 |
| Available until | 31.12.2022 |
Approval - Standards
| Certificates | cULus EAC |
General data
| Standards | IEC 61508 IEC/EN 60204-1 EN 60947-5-1 EN ISO 13849-1 |
| Climatic stress | EN 60068-2-78 |
| Enclosure material | Glass-fibre reinforced thermoplastic, ventilated |
| Gross weight | 140 g |
General data - Features
| Stop-Category | 0 |
| Electronic Fuse | Yes |
| Wire breakage detection | Yes |
| Short-circuit recognition | Yes |
| Removable Terminals | Yes |
| Automatic reset function | Yes |
| Earth connection detection | Yes |
| Integral System Diagnostics, general | Yes |
| Number of auxiliary contacts | 1 |
| Number of LEDs | 5 |
| Number of openers | 1 |
| Number of shutters | 1 |
| Number of safety contacts | 2 |
Safety appraisal
| Standards | EN 60947-5-1 IEC 61508 |
Safety appraisal - Relay outputs
| Performance Level, up to | d |
| Control category to EN13849 | 3 |
| Diagnostic Coverage (DC) Level | 60 % |
| PFH-value | 2.00 x 10⁻⁷ /h |
| Notice | for max. 36,500 switching cycles/year and max. 60% contact load |
| Safety Integrity Level (SIL), suitable for applications in | 2 |
| Mission time | 20 Year(s) |
| Common Cause Failure (CCF), minimum | 65 |
Mechanical data
| Mechanical life, minimum | 10,000,000 Operations |
| Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data - Connection technique
| Terminal Connector | Screw connection, plug-in |
| Terminal designations | IEC/EN 60947-1 |
| Cable section, minimum | 0.14 mm² |
| Cable section, maximum | 1.5 mm² |
Mechanical data - Dimensions
| Width | 48 mm |
| Height | 126 mm |
| Depth | 61 mm |
Ambient conditions
| Degree of protection of the enclosure | IP20 |
| Degree of protection of the mounting space | IP20 |
| Degree of protection of clips or terminals | IP20 |
| Ambient temperature, minimum | -25 °C |
| Ambient temperature, maximum | +55 °C |
| Storage and transport temperature, minimum | -40 °C |
| Storage and transport temperature, maximum | +85 °C |
| Resistance to vibrations to EN 60068-2-6 | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
| Restistance to shock | 30 g / 11 ms |
Ambient conditions - Insulation value
| Rated impulse withstand voltage Uimp | 0.8 kV |
| Overvoltage category | III |
| Degree of pollution to VDE 0110 | 2 |
Electrical data
| Rated operating voltage | 24 VDC -15% / +20%, residual ripple max. 10 % |
| Rated AC voltage for controls at DC minimum | 20.4 VDC |
| Rated control voltage at DC, maximum | 28.8 VDC |
| Electrical power consumption | 1.7 W |
| Input resistance at Ue | 2,900 Ω |
| Contact resistance, maximum | 0.1 Ω |
| Note (Contact resistance) | in new state |
| Drop-out delay in case of emergency stop, maximum | 20 ms |
| Pull-in delay at automatic start, maximum | 20 ms |
Electrical data - Safe relay outputs
| Voltage, Utilisation category DC13 | 24 VDC |
| Current, Utilisation category DC13 | 2 A |
| Switching capacity, minimum | 10 VDC |
| Switching capacity, minimum | 10 mA |
| Switching capacity, maximum | 24 VAC |
| Switching capacity, maximum | 2 A |
Electrical data - Digital inputs
| Input signal, HIGH Signal 1 | 19 - 28,8 VDC |
| Input signal, LOW Signal 0 | 0 - 1 VDC |
| Conduction resistance, maximum | 40 Ω |
Electrical data - Digital Output
| Voltage, Utilisation category DC12 | 24 VDC |
| Current, Utilisation category DC12 | 0.1 A |
Electrical data - Relay outputs (auxiliary contacts)
| Switching capacity, maximum | 24 VDC |
| Switching capacity, maximum | 0.1 A |
Electrical data - Electromagnetic compatibility (EMC)
| EMC rating | EMC-Directive |
Status indication
| Indicated operating states | Position relay K2 Position relay K1 Position relay K3 Position relay K3 |
Other data
| Note (applications) | Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches |