- Suitable for the signal processing of outputs with contact sensors
- Possibility to connect a non-contact end switch or speed reduction switch
- 2 safety contacts, switch-off level 1,
2 safety contacts, switch-off level 2 - 2 Signalling outputs
Ordering data
| Product type description | SRB402NE 230V |
| Article number (order number) | 101178397 |
| EAN (European Article Number) | 4250116202423 |
| eCl@ss number, Version 9.0 | 27-37-18-19 |
| eCl@ss number, Version 11.0 | 27-37-18-19 |
| ETIM number, version 6.0 | EC001449 |
| Replacement article number | 101178532 |
Approval - Standards
| Certificates | EAC |
General data
| Standards | IEC 61508 EN 60947-5-1 EN 60204-1 EN ISO 13849-1 |
| Climatic stress | EN 60068-2-78 |
| Enclosure material | Glass-fibre reinforced thermoplastic, ventilated |
| Material of the contacts, electrical | Ag-Ni, self-cleaning, positive drive |
| Gross weight | 550 g |
General data - Features
| Stop-Category | 0 |
| Wire breakage detection | Yes |
| Short-circuit recognition | Yes |
| Removable Terminals | Yes |
| Feedback circuit | Yes |
| Automatic reset function | Yes |
| Earth connection detection | Yes |
| Integral System Diagnostics, status | Yes |
| Number of auxiliary contacts | 2 |
| Number of LEDs | 7 |
| Number of openers | 4 |
| Number of safety contacts | 4 |
| Number of signalling outputs | 2 |
Safety appraisal
| Standards | IEC/EN 60947-1 IEC 61508 |
Safety appraisal - Relay outputs
| PFH-value | 2.00 x 10⁻⁸ /h |
| Performance level, stop 0, up to | e |
| Category, Stop 0 | 4 |
| Diagnostic Coverage (DC) Level, Stop 0 | ≥ 99 % |
| Safety Integrity Level (SIL), Stop 0, suitable for applications in | 3 |
| Mission time | 20 Year(s) |
| Common Cause Failure (CCF), minimum | 65 |
Mechanical data
| Mechanical life, minimum | 10,000,000 Operations |
| Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data - Connection technique
| Terminal Connector | Screw connection rigid or flexible |
| Terminal designations | IEC/EN 60947-1 |
| Cable section, minimum | 0.25 mm² |
| Cable section, maximum | 2.5 mm² |
| Tightening torque of Clips | 0.6 Nm |
Mechanical data - Dimensions
| Width | 45 mm |
| Height | 100 mm |
| Depth | 121 mm |
Ambient conditions
| Degree of protection of the enclosure | IP40 |
| Degree of protection of the mounting space | IP54 |
| Degree of protection of clips or terminals | IP20 |
| Ambient temperature, minimum | -25 °C |
| Ambient temperature, maximum | +45 °C |
| Storage and transport temperature, minimum | -40 °C |
| Storage and transport temperature, maximum | +85 °C |
| Resistance to vibrations to EN 60068-2-6 | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
| Restistance to shock | 30 g / 11 ms |
Ambient conditions - Insulation value
| Rated impulse withstand voltage Uimp | 4 kV |
| Overvoltage category | III |
| Degree of pollution to IEC/EN 60664-1 | 2 |
Electrical data
| Frequency range | 50 Hz 60 Hz |
| Rated operating voltage | 230 VAC -15% / + 10% |
| Rated AC voltage for controls, 50 Hz, minimum | 195.5 VAC |
| Rated control voltage at AC 50 Hz, maximum | 253 VAC |
| Rated AC voltage for controls, 60 Hz, minimum | 195.5 VAC |
| Rated control voltage at AC 60 Hz, maximum | 253 VAC |
| Electrical power consumption | 6 W |
| Electrical power consumption | 7.8 VA |
| Contact resistance, maximum | 0.1 Ω |
| Note (Contact resistance) | in new state |
| Drop-out delay in case of power failure, typically | 80 ms |
| Drop-out delay in case of emergency, typically | 20 ms |
| Pull-in delay at automatic start, maximum, typically | 100 ms |
| Pull-in delay at RESET, typically | 20 ms |
Electrical data - Safe relay outputs
| Voltage, Utilisation category AC15 | 230 VAC |
| Current, Utilisation category AC-15 | 4 A |
| Voltage, Utilisation category DC13 | 24 VDC |
| Current, Utilisation category DC13 | 4 A |
| Switching capacity, minimum | 10 VDC |
| Switching capacity, minimum | 10 mA |
| Switching capacity, maximum | 250 VAC |
| Switching capacity, maximum | 8 A |
Electrical data - Digital inputs
| Conduction resistance, maximum | 40 Ω |
Electrical data - Relay outputs (auxiliary contacts)
| Switching capacity, maximum | 24 VDC |
| Switching capacity, maximum | 2 A |
Electrical data - Electromagnetic compatibility (EMC)
| EMC rating | EMC-Directive |
Status indication
| Indicated operating states | Position relay K2 Position relay K1 Internal operating voltage Ui Position relay K3 Position relay K5 |
Other data
| Note (applications) | Safety sensor Guard system |
Notes
| Note (General) | Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Circuit example
| Note (Wiring diagram) | The control system recognises wire-breakage and earth faults in the monitoring circuit. The example shows a 1-channel control with contact A for a guard door monitor, of which at least one contact has positive break, with external reset button (R). Relay outputs: Suitable for 1 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. The wiring diagram is shown with non-actuated limit switches and in de-energised condition. (H2) = Feedback circuit |